Electrical Ring Circuit Inspection and Testing - Guide with pictures | SparkyFacts.co.uk


Electrical Ring Circuit Inspection and Testing

The purpose of this test is to ensure that the cables form a complete ring without interconnections between the wires, and the polarity is correct on all outlets.

The best way to do a ring circuit test is with the help of a Resistance Tester or with the Low Reading Ohm meter function of an Installation Tester such as the Megger 1553.

In order to understand this testing procedure you must be familiar with the ring circuit wiring arrangement. You can refresh your knowledge on the ring circuit here.



The Ring Circuit Test sequence:

hintBefore everything, a safe isolation procedure must be carried out.

Step 1. Within the distribution board, remove the Line, the Neutral and the Earth conductors from its terminals. Since this is a ring circuit there will be two of each in the same terminal.

Step 2. Select the low reading ohm meter function and null the tester.

Ring Circuit Test Step 2


Step 3. Measure between Line to Line to get the reading for “r1”

Ring Circuit Test Step 3


Step 4. Measure between Neutral to Neutral to get the reading for “rn”

Ring Circuit Test Step 4


Step 5. Measure between Earth and Earth to get the reading for “r2”

Ring Circuit Test Step 5


Step 6. Connect the first (outgoing) Line to the second (incoming) Earth  and connect the second (incoming) Line to the first (outgoing) Earth (if you cannot see which one is the incoming or the outgoing conductor, just make guess, the testing will show whether you are correct or not).

Ring Circuit Test Step 6


Step 7. Using the low reading ohm meter, test between Line and Earth on every outlet on the ring circuit. The highest reading is the (R1+R2) for the circuit. The readings at each of the sockets wired on the ring should be very similar and the value should be according to this formula: (r1 +r2)/4.   Every time the measured value is deviating by more than 0.5 ohms, the connection at the accessory terminals should be investigated.

Ring Circuit Test Step 7-1Ring Circuit Test Step 7-2


Step 8. Remove the cross connection between the Line and Earth conductors and cross connect the Line and Neutral conductors instead (L1 to N2 and L2 to N1).

Ring Circuit Test Step 8

Step 9. Test between Line and Neutral on every outlet on the ring circuit. The readings at each of the sockets wired on the ring will be very similar and the value should be according to this formula: (r1 +rn)/4.   Every time the measured value is deviating by more than 0.5 ohms, the connection at the accessory terminals should be investigated. 

After these steps you can return the Line, Neutral and Earth conductors back in to its terminals within the distribution board.


The Inspection and Testing C&G 2391 practical exams

Do not forget to record the (R1+R2) value on the Schedule of Test Results.

Next we move on to Insulation Resistance testing.


Important things to remember:

AM2 tipp In a situation when it is not apparent which leg of the ring circuit is the incoming and which one is the outgoing (like the case with single core cables) the tester can only make a guess. The readings taken from every socket or accessory within the ring circuit, will show whether the guess was correct or not. If the readings are progressively increasing in value towards the middle of the ring circuit, and decline in value towards the end - the guess was wrong. The value of the reading should be the same everywhere and within 0.5 ohms of the calculated value.

AM2 tipp In real life situations there could be bonding conductors going to some or all of the accessories on the ring circuit (e.i.: bonding of metallic conduit) which will greatly decrease the measured value of (R1+R2).

AM2 tipp It is common that there are spurs on the ring circuit supplying additional sockets or other accessories. The measured value for (R1 + R2) will be higher for these spurs than the values calculated.

AM2 tipp Remember, that by doing these steps you will also confirm the correct polarity of the conductors, so there is no need to do polarity dead tests again.

hint During the testing remember to constantly inspect the installation for faults and signs of damages.


sparkyfacts


Guides, Tips & Tricks for Electrical Courses, Qualifications and Exams. Copyright © 1998-2018. All Rights Reserved.